Wiring a 220 outlet- can I use a 15 amp outlet with my 20 amp breaker? Or should I get a replacement 15 amp...
I'm trying to wire an outlet for my lathe. The manufacturer recommends a 15 amp breaker. I am planning to run 10 gauge wire approximately 25' to the outlet where I can plug in my lathe. The motor is rated at 8 amps. I currently have an empty 20 amp breaker for 220 in my box. Here are a few pics of what I'm thinking of using.
The first is the plug for the lathe:
The second is the motor specs of the lathe:
Would the following 20 amp outlet work for this?
I've wired 110 but never 220. Also BTW it has a phase converter allowing it to run off 1 phase.
receptacle circuit-breaker 240v
add a comment |
I'm trying to wire an outlet for my lathe. The manufacturer recommends a 15 amp breaker. I am planning to run 10 gauge wire approximately 25' to the outlet where I can plug in my lathe. The motor is rated at 8 amps. I currently have an empty 20 amp breaker for 220 in my box. Here are a few pics of what I'm thinking of using.
The first is the plug for the lathe:
The second is the motor specs of the lathe:
Would the following 20 amp outlet work for this?
I've wired 110 but never 220. Also BTW it has a phase converter allowing it to run off 1 phase.
receptacle circuit-breaker 240v
add a comment |
I'm trying to wire an outlet for my lathe. The manufacturer recommends a 15 amp breaker. I am planning to run 10 gauge wire approximately 25' to the outlet where I can plug in my lathe. The motor is rated at 8 amps. I currently have an empty 20 amp breaker for 220 in my box. Here are a few pics of what I'm thinking of using.
The first is the plug for the lathe:
The second is the motor specs of the lathe:
Would the following 20 amp outlet work for this?
I've wired 110 but never 220. Also BTW it has a phase converter allowing it to run off 1 phase.
receptacle circuit-breaker 240v
I'm trying to wire an outlet for my lathe. The manufacturer recommends a 15 amp breaker. I am planning to run 10 gauge wire approximately 25' to the outlet where I can plug in my lathe. The motor is rated at 8 amps. I currently have an empty 20 amp breaker for 220 in my box. Here are a few pics of what I'm thinking of using.
The first is the plug for the lathe:
The second is the motor specs of the lathe:
Would the following 20 amp outlet work for this?
I've wired 110 but never 220. Also BTW it has a phase converter allowing it to run off 1 phase.
receptacle circuit-breaker 240v
receptacle circuit-breaker 240v
edited Nov 23 at 2:46
200_success
201312
201312
asked Nov 22 at 17:09
Bace Juex
212
212
add a comment |
add a comment |
2 Answers
2
active
oldest
votes
You may know that on 120V circuits, you are allowed to use 15A receptacles on a 20A circuit. This is a special exception that only applies to 15A receptacles only on 20A circuits.
The Code says nothing about voltage.. You can use exactly the same exception on a 240V 20A circuit. You are free to use 15A or 20A receptacles (NEMA 6-15 or 6-20).
If you use a 20A receptacle (NEMA 6-20), the 15A plug will fit in it just fine. They are keyed to do that. (Just the same way as 120V NEMA 5-20 sockets will accept the common NEMA 5-15 plugs.)
There is only one gotcha: if there is only one socket in the whole circuit, the socket size must match the breaker size. So if you use a NEMA 6-15 on your 20A circuit, make sure it's the usual twin-socket receptacle, don't use a one-eye.
1
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
add a comment |
You may be close on the actual power needed if you reduce down to 15 amp protection. the motor is 8 amp 3 phase so if using single phase 240 to power the inverter 1.73 is the factor plus the losses of the inverter and the control starter , work light. since lathes are not a continuous duty device it may work but will be close. I would want to use a 20 amp outlet and keep the 20 amp breaker.
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
add a comment |
Your Answer
StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});
function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});
}
});
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f151115%2fwiring-a-220-outlet-can-i-use-a-15-amp-outlet-with-my-20-amp-breaker-or-should%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
2 Answers
2
active
oldest
votes
2 Answers
2
active
oldest
votes
active
oldest
votes
active
oldest
votes
You may know that on 120V circuits, you are allowed to use 15A receptacles on a 20A circuit. This is a special exception that only applies to 15A receptacles only on 20A circuits.
The Code says nothing about voltage.. You can use exactly the same exception on a 240V 20A circuit. You are free to use 15A or 20A receptacles (NEMA 6-15 or 6-20).
If you use a 20A receptacle (NEMA 6-20), the 15A plug will fit in it just fine. They are keyed to do that. (Just the same way as 120V NEMA 5-20 sockets will accept the common NEMA 5-15 plugs.)
There is only one gotcha: if there is only one socket in the whole circuit, the socket size must match the breaker size. So if you use a NEMA 6-15 on your 20A circuit, make sure it's the usual twin-socket receptacle, don't use a one-eye.
1
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
add a comment |
You may know that on 120V circuits, you are allowed to use 15A receptacles on a 20A circuit. This is a special exception that only applies to 15A receptacles only on 20A circuits.
The Code says nothing about voltage.. You can use exactly the same exception on a 240V 20A circuit. You are free to use 15A or 20A receptacles (NEMA 6-15 or 6-20).
If you use a 20A receptacle (NEMA 6-20), the 15A plug will fit in it just fine. They are keyed to do that. (Just the same way as 120V NEMA 5-20 sockets will accept the common NEMA 5-15 plugs.)
There is only one gotcha: if there is only one socket in the whole circuit, the socket size must match the breaker size. So if you use a NEMA 6-15 on your 20A circuit, make sure it's the usual twin-socket receptacle, don't use a one-eye.
1
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
add a comment |
You may know that on 120V circuits, you are allowed to use 15A receptacles on a 20A circuit. This is a special exception that only applies to 15A receptacles only on 20A circuits.
The Code says nothing about voltage.. You can use exactly the same exception on a 240V 20A circuit. You are free to use 15A or 20A receptacles (NEMA 6-15 or 6-20).
If you use a 20A receptacle (NEMA 6-20), the 15A plug will fit in it just fine. They are keyed to do that. (Just the same way as 120V NEMA 5-20 sockets will accept the common NEMA 5-15 plugs.)
There is only one gotcha: if there is only one socket in the whole circuit, the socket size must match the breaker size. So if you use a NEMA 6-15 on your 20A circuit, make sure it's the usual twin-socket receptacle, don't use a one-eye.
You may know that on 120V circuits, you are allowed to use 15A receptacles on a 20A circuit. This is a special exception that only applies to 15A receptacles only on 20A circuits.
The Code says nothing about voltage.. You can use exactly the same exception on a 240V 20A circuit. You are free to use 15A or 20A receptacles (NEMA 6-15 or 6-20).
If you use a 20A receptacle (NEMA 6-20), the 15A plug will fit in it just fine. They are keyed to do that. (Just the same way as 120V NEMA 5-20 sockets will accept the common NEMA 5-15 plugs.)
There is only one gotcha: if there is only one socket in the whole circuit, the socket size must match the breaker size. So if you use a NEMA 6-15 on your 20A circuit, make sure it's the usual twin-socket receptacle, don't use a one-eye.
answered Nov 22 at 18:14
Harper
65.1k342133
65.1k342133
1
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
add a comment |
1
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
1
1
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
Hey thanks! That clears things up. Would this outlet be appropriate to match? It's a 20 amp, just has an extra T in it, I'm guessing to designate that its 20 amp?homedepot.com/p/…-PIPHorizontal2_rr--301207379--100356999--N
– Bace Juex
Nov 22 at 19:47
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
The T allows it to take both 15A and 20A plugs.
– Peter Green
Nov 23 at 0:11
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
@BaceJuex yes, that will be fine, just make sure it's on a 20A breaker. They also make those in duplex if you want two sockets.
– Harper
Nov 23 at 0:55
add a comment |
You may be close on the actual power needed if you reduce down to 15 amp protection. the motor is 8 amp 3 phase so if using single phase 240 to power the inverter 1.73 is the factor plus the losses of the inverter and the control starter , work light. since lathes are not a continuous duty device it may work but will be close. I would want to use a 20 amp outlet and keep the 20 amp breaker.
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
add a comment |
You may be close on the actual power needed if you reduce down to 15 amp protection. the motor is 8 amp 3 phase so if using single phase 240 to power the inverter 1.73 is the factor plus the losses of the inverter and the control starter , work light. since lathes are not a continuous duty device it may work but will be close. I would want to use a 20 amp outlet and keep the 20 amp breaker.
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
add a comment |
You may be close on the actual power needed if you reduce down to 15 amp protection. the motor is 8 amp 3 phase so if using single phase 240 to power the inverter 1.73 is the factor plus the losses of the inverter and the control starter , work light. since lathes are not a continuous duty device it may work but will be close. I would want to use a 20 amp outlet and keep the 20 amp breaker.
You may be close on the actual power needed if you reduce down to 15 amp protection. the motor is 8 amp 3 phase so if using single phase 240 to power the inverter 1.73 is the factor plus the losses of the inverter and the control starter , work light. since lathes are not a continuous duty device it may work but will be close. I would want to use a 20 amp outlet and keep the 20 amp breaker.
answered Nov 22 at 17:38
Ed Beal
30.8k12144
30.8k12144
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
add a comment |
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
Thanks all, very helpful, just had to re read a couple times. I think I'll go with the 20 amp receptacle.
– Bace Juex
Nov 22 at 20:08
add a comment |
Thanks for contributing an answer to Home Improvement Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Some of your past answers have not been well-received, and you're in danger of being blocked from answering.
Please pay close attention to the following guidance:
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f151115%2fwiring-a-220-outlet-can-i-use-a-15-amp-outlet-with-my-20-amp-breaker-or-should%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown